Page 1 of 4 PR115 rev-2011-09-02 4.1 Total measured duct leakage to meet ENERGY STAR standards 1. With air-handler off, conn
Page 2 of 4 4.2 Measured duct leakage to outdoors to meet ENERGY STAR standards If Total Leakage is above 4, perform this test which measures le
Page 3 of 4 4.3 Envelope leakage test to meet ENERGY STAR standards 1. Remove Grill Mask and DucTester. 2. Connect the Door Fan to blow outdoo
Page 4 of 4 Gauge set up to meet ENERGY STAR standards The first time you use the DM-2, press [Auto Zero] to turn it “On,” and press [Time Avg] unti