Make sure DucTester 340 is showing on the
Home screen.
If not, tap the fan picture, then
Tap
, tap DucTester 340, then select the
range that you have installed.
Tap on [Channel B] to change the type of result
or units. Select based on “Get the results you
need” on page 4.
Tap [Settings] then [Time averaging] and
select 5 seconds.
Tap [Settings] then .
Make sure the [Default @ Pressure] is 25 Pa.
Tap to return to the Home screen.
Adjust fan speed knob clockwise
until [Channel A] reaches test pressure.
Usually -25 Pa.
If you cannot achieve the test pressure,
refer to page 4.
Now connect the Speed Control Cable
to allow the gauge to control the
speed. Solid green Status light indicates
gauge is ready to control the speed.
For a test pressure of
25 Pa, tap
Enter 25, tap [Set]
Tap
to display what the
result would be at
exactly 25 Pa
.
Page 3 of 4
Read results directly from
the gauge.
Tubing connections:
Step 4: Prepare the gauge
Total Duct Leakage Test: Depressurize
Step 5: Conduct test
Speed Control Cable
Step 3: Connect gauge & fan (cont’d)
Press on the gauge, then tap the screen, and
check the battery state indicator at the top right:
If the battery display is not green, connect
USB to power outlet to charge the gauge.
Connect yellow, green and blue tubes
to the gauge.
Channel A
Channel B
Connect the
gauge
like this for
all tests.
219.9
219.9