However, if it was known that n was 0.7, the flow at 25 should have been:






 
This value is less than 3% off from what it should be. If the test pressure was within 1 or 2 Pa of the
reference pressure of 25 Pa, the @ Pressure reading would be exact.
To change the n value
1. Press [Setup] to access the Setup menu.
2. Press [] or [] to select "n" in the list. Press [Enter].
3. Input the new value between 0.5 and 1. Press [Enter].
Power Down Hour
The Power Down Hour helps to maximize battery power by enabling the DM-2 to automatically turn off
when it has been inactive for a set time period. The feature can be set to any value between 0 and 255
hours. Applying a 0 value will disable the Power Down feature, and the DM-2 will never automatically
shut down.
To change the Power Down Hour
1. Press [Setup] to access the Setup menu.
2. Press [] or [] to select "Power Down Hour" in the list. Press [Enter].
3. Input the new value. Press [Enter].
Surface Area Unit
For some results (e.g. Flow/Area, EqLA/Area, Hole Flow) an area measurement is required to calculate
them. The units used for area can be configured. The area units may be set to square feet (ft
2
), square
meters (m
2
), square centimeters (cm
2
), or square inches (in
2
).
To change the Area units
1. Press [Setup] to access the Setup menu.
2. Press [] or [] to select "Surface Area Unit" in the list.