5.7 Setting up for a test with Alaska’s AkWarm software
1. Press [Setup] to enter the Setup menu
2. Press [] or [] to scroll through the list until “Mode Setup” is highlighted
3. Press [Enter] to enter the Mode Setup submenu
4. Press [] or [] to scroll until “Pressure” is highlighted.
5. Press [] or [] to scroll until “Pa” is displayed
6. Press []to highlight “Flow”
7. Press [] or []to scroll until “CFM” is displayed
8. Press [] once to highlight “EqLA”
9. Use [] or [] to scroll until “in
2
” or” ft
2
” is displayed (this is an optional measurement
forAlaska AkWarm)
10. Press [] once to highlight “Air Change”
11. Use [] or [] to scroll until “On” is displayed (this is an optional measurement for Alaska
AkWarm)
12. Scroll down to all other results in the Mode Setup menu, and use [] or [] to scroll until “Off”
is displayed to disable all other results.
13. Press [Exit] once to return to the Setup submenu
14. Press [] to select “n”
15. Press [Enter]
16. Use the keyboard to set this value to “0.65”
17. Press [Enter] to accept this value
18. Press [] to select “Power Down Hour”
19. Leave at “2” (hours) or set to “0” to turn auto-power-down off.
20. Press [] to select “Surface Area Unit”
21. Press [] or [] to set to “ft
2
”
(Note: AKWarm does not require the use of this parameter)
22. Press [] to select “Building Volume Unit”
23. Press [] or [] to set to “ft
3
”
(Note: when you select Air Changes, you will enter volume in
ft
3
)
24. Press [] to select “European , Separator”
25. Press [] or [] to set to “No”
26. Press [] to select “Sig Figs”
27. Press [] or [] to set to “3.5”
28. Press [Exit] to exit the Setup menu and save these Setup settings.
Your DM-2 is now set up for performing an Air Leakage Test with Alaska’s AKWarm Software.