Appendix B: Cannot Reach @ Pressure Factors
Cannot Reach 50 Pa Factors
Take CFM reading at pressure achieved and multiply by "Cannot reach 50 factor" to get pressure at 50
Pa. e.g. read 1000 CFM at building pressure of 30 Pa. Factor is 1.36,
1000 x 1.36 = 1360 CFM
Table 10. Factors for when a building pressure of 50 Pa cannot be reached (“n” value of 0.65).
Pressure
achieved
Cannot reach
50 factor
Pressure
achieved
Cannot reach
50 factor
50
1.00
25
1.57
49
1.01
24
1.61
48
1.03
23
1.66
47
1.04
22
1.71
46
1.06
21
1.76
45
1.07
20
1.81
44
1.09
19
1.88
43
1.10
18
1.94
42
1.12
17
2.02
41
1.14
16
2.10
40
1.16
15
2.19
39
1.18
14
2.29
38
1.20
13
2.40
37
1.22
12
2.53
36
1.24
11
2.68
35
1.26
10
2.85
34
1.28
9
3.05
33
1.31
8
3.29
32
1.34
7
3.59
31
1.36
6
3.97
30
1.39
5
4.47
29
1.42
28
1.46
27
1.49
26
1.53