5.6 Using the DM-2 to look for the locations of Leaks
If your test does not comply (e.g. the retention time is less than what is required) with the Standard
you are testing against (e.g. NFPA 2001), you need to search where the leakage locations are in the
enclosure, seal up the leakages, and run the Enclosure Integrity Test again.
The following instructions describe how to measure the total leakage area of the enclosure while
sealing up leaks to pass the Enclosure Integrity Test:
1. If you are not already in Set Pressure mode (for example, you used Method 2 to achieve your
target pressure) then press [Set Pressure] and input the current target pressure.
2. Press [Mode] until EqLA appears on the display beside the Mode label on the DM-2.
(Enable EqLA in the Mode Setup if EqLA does not appear after cycling through [Mode])
3. If the units for EqLA indicate ft
2
or in
2
“@ 50Pa”, then press [@Pressure] until the @ qualifier
disappears. The DM-2 now displays the total leakage area of the enclosure.
4. If the displayed leakage is small, and the units for EqLA are in ft
2
you might want to switch the
units to in
2
in the Setup menu. If the leakage is large and you are in in
2
, you might want to
switch the units to ft
2
.)
5. Search for, locate, and temporarily seal holes in the enclosure. You will hear the fan slow down
(less flow is required to achieve the target pressure when the room is tighter).
6. The retention tab in Retrotec’s CA2001 software indicates the Maximum AllowableELA. If
the EqLA reading on the DM-2 is greater than what is the “Maximum Allowable ELA” on
CleanAgent 2001, you must continue sealing leaks in order to get the EqLA reading on the
gauge to be less than what is the “Maximum Allowable ELA” is specified for your test on
CleanAgent 2001.
7. When the EqLA reading on the DM-2 is less than the “Maximum Allowable ELA” on the
CleanAgent 2001, you have passed the Enclosure Integrity Test. (According to NFPA 2001, this
translates to what the Maximum Allowable ELA should be to have a retention time of at least
10 minutes)